RP (RPZ) vs Double Check (DC/DCVA) vs PVB and SVB: Backflow Assembly Types Explained
The backflow assemblies California testers see most, RP/RPZ, DC/DCVA, DCDA, RPDA, PVB and SVB, what each protects against and where each is used, from the State Water Board's definitions.
Your test notice probably names your assembly with an abbreviation. Here's what each one means, using the State Water Board's definitions in the Cross-Connection Control Policy Handbook (CCCPH) and plain-English descriptions from California utilities.
| Assembly | What's inside | Protects against | Hazard level (CCCPH) |
|---|---|---|---|
| RP / RPZ / RPP Reduced pressure principle | Two independent check valves with a differential-pressure relief valve between them | Backpressure and backsiphonage | High or low hazard. The handbook's high-hazard premises list calls for an air gap or an RP. |
| DC / DCVA Double check valve | Two independent check valves, shutoff valves at each end, test cocks | Backpressure and backsiphonage | Low hazard only |
| DCDA / DCDA-II Double check detector | A DC with a metered bypass that registers even small flows | Same as DC | Low hazard only. Common on fire lines. |
| RPDA / RPDA-II Reduced pressure detector | An RP with a metered bypass | Same as RP | Common on fire lines that are a health hazard |
| PVB Pressure vacuum breaker | One check valve plus a loaded air inlet valve on the discharge side | Backsiphonage only, not backpressure | Used where only backsiphonage is possible, such as many irrigation systems |
| SVB Spill-resistant vacuum breaker | Like a PVB, designed to resist spilling, with a test cock and bleed/vent port | Backsiphonage only | Same uses as a PVB |
Sources: CCCPH definitions and Appendix D; Golden State Water's assembly descriptions. "RPZ" and "RPP" are common names for the RP. "DCVA" is a common name for the DC.
RP (RPZ): the high-hazard workhorse
The reduced pressure principle assembly has two check valves with a relief valve between them. If either check leaks, the relief valve opens and dumps water out the bottom rather than letting it flow backward. That's why you sometimes see an RP discharging water, which is a sign it needs a tester's attention. Golden State Water describes the RP as protecting against both health and non-health hazards under backpressure and backsiphonage.
The CCCPH's Appendix D lists premises that need an air gap or an RP, including medical and dental facilities with water-connected equipment, car washes, hotels and motels, gas stations, mobile home and RV parks, agricultural premises, laboratories, business parks with a single meter serving multiple businesses, and sites with an auxiliary water supply such as a well.
DC (double check): low hazard only
A double check has two independently acting check valves and no relief valve. The CCCPH says it "may only be used to isolate low hazard cross-connections." For residences using recycled water for landscape irrigation in an approved dual-plumbed area, the handbook sets a DC as the minimum.
DCDA and RPDA: detector assemblies on fire lines
Detector assemblies add a small metered bypass so the utility can see slow leaks or unauthorized water use on lines that should sit idle. Golden State Water says the DCDA is commonly used on fire protection systems that pose a non-health hazard, and the RPDA on fire systems that pose a health hazard. See our irrigation and fire line guide.
PVB and SVB: irrigation, backsiphonage only
A pressure vacuum breaker has one check valve and an air inlet that opens to break a vacuum. The CCCPH says a PVB "may only be used for protection from backsiphonage and is not to be used to protect from backpressure." The SVB works the same way and is built to resist spilling. Both are testable assemblies, so they're on the annual cycle too.
What isn't a testable assembly
A hose bib vacuum breaker, the small screw-on device on an outdoor faucet, is a non-testable device. Golden State Water recommends them on hose connections, but they're not what your annual notice is about. An air gap, a physical space between the supply outlet and the receiving vessel, is the most protective method. The CCCPH requires air gaps to be inspected visually at least once a year.
Does the type change the test?
Yes. Each type has its own field test procedure, and report forms have separate sections for the RP, DC and PVB parts. Every type still needs a certified tester and is on the same annual cycle. Use the deadline checker to see what your district needs.
Need a certified tester?
Check your deadline, or get matched with a tester who serves your water district.
FAQ
Is an RPZ the same as an RP?
Yes. RPZ (reduced pressure zone) and RPP are common names for the reduced pressure principle (RP) assembly defined in the State Water Board's handbook.
Can a double check be used for a high-hazard site?
No. The CCCPH says a DC may only be used to isolate low hazard cross-connections. High-hazard premises need an air gap or an RP unless the water system decides otherwise after a hazard assessment.
Does a PVB need annual testing?
Yes. A PVB is a testable backflow prevention assembly, so it falls under the annual field-test requirement.