Repairs
Failed Backflow Test? What Happens Next and Your Repair Options
What a failed backflow test means in California, the 30-day repair-or-replace rule in the State Water Board's handbook, repair vs replacement, and retesting.
A failed backflow test is common and fixable. It means one or more internal parts didn't hold pressure the way they should. Here's what California's rules say happens next.
The 30-day rule
The State Water Board's Cross-Connection Control Policy Handbook (CCCPH), section 3.3.3(e), says water systems must make sure assemblies that fail are "repaired or replaced within 30 days of notification of the failure." A water system can allow extensions if its own cross-connection control plan includes them. Some utilities repeat the rule. IRWD's regulations, for example, say a defective device must be repaired or replaced within 30 days at the customer's expense.
Repair or replace?
Most failures are repaired, not replaced. Utility test forms show what's typically serviced. IRWD's and Riverside's reports have checkboxes for cleaning or replacing discs, O-rings, springs, seats, diaphragms, modules and test fittings, then a "final test" section for after repairs.
Replacement comes up when an assembly is beyond repair, no longer an approved model, or the wrong type for the hazard. Things to know:
- Your utility may decide the type. LADWP's Rule 16-D says the consumer must notify the Department before replacing an assembly, and the Department decides the meter protection required.
- Older approvals don't last forever. EBMUD says assemblies installed with its earlier approval can keep being tested until they're no longer repairable, and then must be upgraded to current standards.
- Permits may apply. SJW and EBMUD both note that city or county plumbing permits may be required for installations.
- Some utilities share the repair work. The City of Fresno says failed RPP devices are repaired by qualified testing agencies or Water Division staff, and devices beyond repair must be replaced by the owner.
Retest after repair
The CCCPH requires a field test after any repair (section 3.3.3(a)). LADWP's rule adds that an assembly needing repairs isn't considered compliant until a certified tester approves it for operation. Many testers repair and retest on the same visit when they carry parts. Ask about that when you book.
What to ask your tester
- Which part failed, and what reading did it show?
- Can it be repaired today, and will you retest and file both the initial and final results?
- If it needs replacing, does my utility need to approve the type first? Is a permit needed?
- When will the report be filed, and can I get a copy?
Don't ignore a dripping RP
If a reduced pressure (RP) assembly is discharging water from its relief valve, that's a sign something inside isn't holding. Have a tester look at it rather than waiting for the next annual notice. Testers must also tell the utility within 24 hours if they see a backflow incident or an unprotected cross-connection during testing (CCCPH 3.3.3(f)).
We don't publish repair prices. Costs depend on the part, assembly size and access. get matched with a certified tester, or check your deadlines with the deadline checker.
Need a certified tester?
Check your deadline, or get matched with a tester who serves your water district.
FAQ
How long do I have to fix a failed backflow preventer in California?
The State Water Board's handbook says failed assemblies must be repaired or replaced within 30 days of notification of the failure, unless your water system's plan allows an extension.
Do I need a retest after a backflow repair?
Yes. The CCCPH requires a field test after repair, and utilities such as LADWP don't treat the assembly as compliant until a certified tester approves it.
Can my tester fix the assembly on the same visit?
Often, if they carry the parts. Utility report forms have both initial and final test sections for this reason.
Sources
- State Water Board, Cross-Connection Control Policy Handbook (CCCPH), amended April 21, 2026 (PDF)
- IRWD Rules and Regulations, adopted June 9, 2025 (PDF)
- Riverside Public Utilities Water Rule 13 (PDF)
- LADWP Water Service Rule 16-D, revised July 1, 2025 (PDF)
- EBMUD: Backflow prevention
- San Jose Water: Backflow Testing Changes January 2027
- City of Fresno: Water Quality and Testing